Why Your Generator Won't Start: The Faults Behind Most Callouts

The most common reasons a generator cranks but will not fire, runs then stops, produces no power, or stays completely dead — and how each one is diagnosed.

A generator that will not start is almost always suffering from one of a handful of faults. Working through them in order saves time and money.

If the engine does not crank at all, suspect the battery first — it is the most common cause by a wide margin. Standby batteries self-discharge when idle, and a failed battery charger, corroded terminals or an aged battery will all leave you with a machine that does nothing when the power fails. Check for 12 or 24 volts at the terminals, then have the battery load tested rather than trusting a voltage reading alone. Also check the emergency stop button, the control panel fuses, the key switch or start relay, and the safety interlocks on the canopy doors.

If the engine cranks but does not fire, the problem is usually fuel or ignition. On diesel units, look for air in the system after a filter change or a run-dry, a blocked fuel filter, a stuck fuel solenoid, a failed lift pump, or a contaminated tank feeding water and dirt into the injection pump. Bleeding the fuel system correctly solves many of these. On petrol units, a carburettor full of varnished fuel after months of standing is the classic culprit; ignition coils, spark plugs and the oil-level cut-out are the other frequent offenders.

If the engine starts and then stops within seconds, suspect the oil pressure or coolant temperature protection circuits, a faulty stop solenoid, or the controller losing its run signal.

If it runs but produces no power, the fault has moved to the alternator or its excitation: a failed AVR, worn brushes, a broken rotating diode, or lost residual magnetism after long storage. These are all repairable, and rewinding is normally far cheaper than replacing the alternator.

Finally, if the generator runs and produces power but cannot carry the load, it is usually a sizing problem, a governor fault or a partially failed alternator. A load bank test will tell you which. Bring us the symptoms and the hour meter reading and we will diagnose it properly.